Features:
- Long Life
- High Flame Retardant Properties
- Excellent resistance to moisture, abrasion, grease & oil
- Excellent mechanical & electrical properties
- Steam and boiling water resistant
- Non Corrosive & non toxic insulation


Our pipes, hoses & fittings are specially design for industrial usage. Our product gives best performance while use in the factory. Due to high durability & flexibility our pipes & hoses are famous for industrial usage.
The pipes, hoses & fittings are light in weight which results in extensive saving of time and laboring being Abrasion/Chemical resistance, free from rusting, pitting or scaling and maintenance-free.
The pipes are specially designed for desire application which meets the required results as follows:
| ADDITIONAL FR PROPERTIES | ADDITIONAL FR-LSH PROPERTIES | ||||
|---|---|---|---|---|---|
| Test | Test Method | Values | Test | Test Method | Values |
| Limited Oxygen Index | IS 10810 P- 58 | >29% | Limited Oxygen Index | S 10810 P-58 | >29% |
| Limited Temperature Index | IS 10810 P-64 | > 250·c | Limited Temperature Index | IS 10810 P-64 | > 250·c |
| Smoke Density (Light Absorption) | IS 13360 P6/Sec 9 | <60% | |||
| Acid Gas Generation | IS 10810 P-59 | < 20% | |||
| SINGLE CORE PVC INSULATED UNSHEATHED ELECTROLYTIC COPPER WIRES UP TO 11 00V AS PER IS 694: 0JIJ | |||||
|---|---|---|---|---|---|
| Nominal c/s Area of Conductor In sq. mm. | Conductor Construction No.Imm | Nominal InsulationThickness In mm | Approx. Overall Dia. In mm | Current Rating At 40'C In Amps(#) | Max, D/C Resistance Per km.@ 20'C Ohm./km(•) |
| 0.50 | 16/0.20** | 0.6 | 2.2 | 4 | 39.0 |
| 0.75 | 24/0.20** | 0.6 | 2.5 | 7 | 26.0 |
| 1.00 | 14/0.30** | 0.7 | 2.7 | 11 | 18.1 |
| 1.50 | 14/0.30** | 0.7 | 2.7 | 11 | 18.1 |
| 2.50 | 36/0.30** | 0.8 | 3.5 | 18 | 7.41 |
| 4.00 | 56/0.30** | 0.8 | 4.2 | 26 | 4.95 |
| SINGLE CORE PVC UNSHEATHED ELECTROLYTIC COPPER INDUSTRIAL FLEXIBLE CABLES UP TO 1100 V.AS PER IS 694:2010 | |||||
|---|---|---|---|---|---|
| Nominal c/s Area of Conductor In sq. mm. | Conductor Construction No.Imm | Nominal InsulationThickness In mm | Approx. Overall Dia. In mm | Current Rating At 40'C In Amps(#) | Max, D/C Resistance Per km.@ 20'C Ohm./km(•) |
| 6.00 | 84/0.30** | 0.8 | 5.0 | 31 | 3.30 |
| 10.00 | 140/0.30** | 1.0 | 6.2 | 42 | 1.91 |
| 16.00 | 226/0.30** | 1.0 | 7.5 | 57 | 1.21 |
| 25.00 | 354/0.30** | 1.2 | 9.0 | 72 | 0.780 |
| 35.00 | 495/0.30** | 1.2 | 10.4 | 90 | 0.554 |
| 50.00 | 708/0.30** | 1.4 | 13.0 | 115 | 0.385 |
| 70.00 | 988/0.30** | 1.4 | 16.0 | 165 | 0.272 |
| 95.00 | 1349/0.30** | 1.6 | 18.0 | 200 | 0.206 |
| 120.00 | 608/0.30** | 1.6 | 20.2 | 225 | 0.161 |